Fault Codes - Maintenance Warnings :
The air conditioner provides information to the user before failure by the error codes. When you see an error code, please do maintenance care.
COMPRESSOR FAILURE, when the compressor works for 10 min., if the evaparator sensor value does not decrease more than 3 °C from the value at which the compressor is activated, the error occurs. Alarm relay is activated, Compressor stops. Cooling Error, Gas Leakage or Compressor Failure. Detail Document (PDF)
Condanser Sensor Alarm occurs, when the condenser sensor value exceeds 75 °C. Alarm relay is activated, Compressor stops. Reasons:
A) The condenser unit is extremely dusty, sufficient air cannot be passed through. Clean the condenser unit with compressed air.
B) Condenser fan is defective.
Evaporator Sensor Alarm occurs, when Evaporator sensor value falls below 3 °C. Alarm relay is activated, Compressor stops. Reasons:
A) The evaporator unit is extremely dusty, sufficient air cannot be passed through. Clean the evaporator unit with compressed air.
B) The evaporator fan is defective.
This alarm occurs when the cabinet internal temperature is greater than the 'Set + High Temp Point' parameter. It notifies that the internal temperature of the cabinet exceeds the alarm level, the alarm relay is activated.
HIGH TEMP SET and HIGH TEMP POINT parameters can be set at MENU-2.
Door open alarm. When this error occurs, compressor and fan. Check the door switch cables from the power connection terminal. If you have not connected a door switch, enter menu-2 with the SET and R keys and change the Door Switch Relay parameter NO/NC.
If the Reset (R) button is pressed for 3 seconds, the device goes to OFF mode. If the Reset (R) button is pressed for 3 seconds while OFF is written on the display, the unit goes back into operating mode.
The cabinet Sensor Break / No Contact
The condanser Sensor Break / No Contact
The evaporator Sensor Break / No Contact